FP9-C40PV 600V 2P Surge Protection Device(SPD)

FP9-C40PV 600V 2P Surge Protection Device(SPD)

Low Voltage Protection Devices, Solar Energy Equipments, SPD FOR PV, Surge Protection Device

APPLICATION:

This DC surge protective device is applied low voltage standard IEC EN 61643-11 to protect against DC power line system and other equipment from over-voltage and instantaneous over-voltage damage. Widely used in photovoltaic comber box, power inverter, DC distribution cabinet, etc. It has the advantages of a large discharge current, fast response time, and low residual voltage. Max. PV voltage up to UCPV ≤1000V dc.

MAIN FEATURES:

1. High discharge capacity, quick response, module pluggable;

2. Fast response time, din rail installation;

3. Double thermal disconnection devices, provide more reliable protection; 4. Green window means normal, red means defect, need to change module;

5. Remote alarm terminal optional.

6. T1+T2 surge protection.

Type
SPD according to EN 61643-31 / IEC 61643-31type 1+2 / class I+II
Max. continuous operating DC voltage600 V DC
  (DC+)-PE,(DC-)-PE  ,(DC+)-(DC-)  Ucpv
Nominal discharge current (8/20μs) In20 kA
Maximum discharge current (8/20μs) Imax40 kA
Maximum impulse current (8/20μs) Itotal40 kA
Maximum impulse current (10/350μs) Iimp6.25 kA
Maximum impulse current (10/350μs) Itotal12.5 kA
continuous current for PV application ICPV0.2 mA
Voltage protection level (DC+)-PE,(DC-)-PE  (DC+)-(DC-) Up2.2 kV
Response time tA25 ns (L-N)
Short-Circuit Current Rating Iscpv2000 A
Residual current a.c. and d.c.           IPE0.3 mA(DC), 0.3 mA(AC),
Humidity range5% … 95%
Range of operating temperatures TU-40°C … +70°C
Atmospheric pressure and altitude80k Pa … 106k Pa,
-500 m … 2000 m
Operating state / fault indicationGreen ok / Red defect
Number of portsOne port
Cross-sectional area (max.)2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35 mm2 (Solid, Stranded) / 25 mm2 (Flexible)
For mounting on35 mm DIN rail acc. to EN 60715
Enclosure materialthermoplastic
Place of installationindoor installation
Degree of protectionIP 20
Capacity4 module(s), DIN 43880
Approvals
Type of remote signalling contactchangeover contact
a.c. switching capacity250V / 0.5 A
d.c. switching capacity250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signallingmax. 1.5 mm2 solid / flexible
terminals
Remote signalling alarming modeNormal: closed;
failure: open-circuit
AcessibilityInaccessible
Protection fuctionOvercurrent
PV earthing systemEarthed and Unearthed (both)
SPD failure mode (OCFM/SCFM)OCFM


 