FP9-C40PV 1500V 3P Surge Protection Device(SPD)

FP9-C40PV 1500V 3P Surge Protection Device(SPD)

FP9-C40PV 1500V 3P Surge Protection Device(SPD)

Type
SPD according to EN 61643-31 / IEC 61643-31type 1+2 / class I+II
Max. continuous operating DC voltage1500 V DC
  (DC+)-PE,(DC-)-PE  ,(DC+)-(DC-)  Ucpv
Nominal discharge current (8/20μs) In20 kA
Maximum discharge current (8/20μs) Imax40 kA
Maximum impulse current (8/20μs) Itotal40 kA
Maximum impulse current (10/350μs) Iimp6.25 kA
Maximum impulse current (10/350μs) Itotal12.5 kA
continuous current for PV application ICPV0.2 mA
Voltage protection level (DC+)-PE,(DC-)-PE  (DC+)-(DC-) Up5.0 kV
Response time tA25 ns (L-N)
Short-Circuit Current Rating Iscpv2000 A
Residual current a.c. and d.c.           IPE0.3 mA(DC), 0.3 mA(AC),
Humidity range5% … 95%
Range of operating temperatures TU-40°C … +70°C
Atmospheric pressure and altitude80k Pa … 106k Pa,
-500 m … 2000 m
Operating state / fault indicationGreen ok / Red defect
Number of portsOne port
Cross-sectional area (max.)2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35 mm2 (Solid, Stranded) / 25 mm2 (Flexible)
For mounting on35 mm DIN rail acc. to EN 60715
Enclosure materialthermoplastic
Place of installationindoor installation
Degree of protectionIP 20
Capacity4 module(s), DIN 43880
Approvals
Type of remote signalling contactchangeover contact
a.c. switching capacity250V / 0.5 A
d.c. switching capacity250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signallingmax. 1.5 mm2 solid / flexible
terminals
Remote signalling alarming modeNormal: closed;
failure: open-circuit
AcessibilityInaccessible
Protection fuctionOvercurrent
PV earthing systemEarthed and Unearthed (both)
SPD failure mode (OCFM/SCFM)OCFM


 