FM1L Earth-leakage Circuit Breaker (ELCB)

FM1L Earth-leakage Circuit Breaker (ELCB)

FMIL series Earth-leakage circuit breaker (ELCB) is suitable for AC 50/60Hz, rated voltage 230/400V, rated current 1-63A lines, with leakage, shock, overload, short circuit protection functions. When the leakage current exceeds the prescribed current value, the product cut off the fault current within 0.1s, protect personal safety and prevent the accident caused by the leakage current of equipment, and can be used to protect the overload and short circuit of the line. Under normal circumstances, it can be used as an infrequent disconnection and conversion of the line. It is mainly used in the protection of building lighting and distribution systems.

FEATURES

Rated current In1-63A
Poles1P+N,2P,3P+N,4P
Rated voltage Ue230/400V~
Insulation voltage Ui500V
Rated frequency50/60Hz
Rated sensitivity IAn0.03A 0.1A 0.3A
Rated residual making and breaking capacity I m500(In=25-40A) 630(In=63A)
Short-circuit current Inc=lAc6000A
SCPDfuse6000
Break time underIAn≤0.1S
Rated impulse withstand voltage(1.2/50)Uimp6000v
Dielectric test voltage at and find. freq.for 1min2.5kV
Pollution degree2
Thermo-magnetic release characteristicB、C
Electrical life4000
Mechanical life10000
Installation
Contact position indicatorYes
Protection degreeIP20
Reference temperature for the setting of the thermal element30℃
Ambient temperature (with a daily average ≤of 35℃)-5~+40℃
Storage temperature-25~+70℃
Terminal connection typeCable/U-type busbar/Pin-type busbar
Terminal size top/bottom for cable25mm²18-3
Tightening torque3.0N*m 22
MountingOn DIN rail FN 60715(35mm) by means of the fast clip device
ConnectionTop and bottom


 