FNX2-F series Telemechanic Contactor

FNX2-F series Telemechanic Contactor

1. General

FNX2-F series AC contactor is applicable in the circuit rated voltage up to 1000V AC. 50/60Hz, rated current up to 780A, for long distance breaking circuit and frequency starting or controlling the motor. FNX2-F Series Telemechanic Contactor also can be used for the control of distributing circuits of rated current from 200A to 1600A(AC-1)/115A to 780A(AC-3). The products comply with IEC 60947-4.

 

2. Type designation

 

Name

Rated current

Auxiliary contact

Pole number

Coil voltage

Frequency

FNX2-F

115—780

3,4

48—66

50/60

 

Rated current (A)

Auxiliary contact

Type

Normal open (NO)

Normal close (NC)

115

FNX2-F11500*

150

FNX2-F15000*

185

FNX2-F18500*

225

FNX2-F22500

265

FNX2-F26500

330

FNX2-F33000*

400

FNX2-F40000

500

FNX2-F50000

630

FNX2-F63000*

Note: 3 Pole is normal type, not remarked in the type name.

 

 

3. Specifications of FNX2-F Series Telemechanic Contactor

Type



FNX2-F115

FNX2-F150

FNX2-F185

FNX2-F225

FNX2-F265

FNX2-F330

FNX2-F400

FNX2-F500

FNX2-F630

Main circuit characteristic


Poles

3P.4P

Rated operation voltage (Ue)


V

380 600 1000

Rated insulation voltage (Ui)


V

1000

Rated heating current (Ith)


A

200

200

275

275

315

380

450

630

800

Rated operation current (Ie)

AC-3 380V

A

115

150

185

225

265

330

400

500

630

AC-3 660V

A

86

108

118

137

170

235

303

353

462

AC-3 1000V

A

46

51

71

90

112

115

200

232

331

AC-4 380V

A

52

60

79

85

105

117

138

147

188

AC-4 660V

A

49

61

69

82

98

118

135

145

170

Max.power of 3 phase motor controlled

AC-3 220V

Kw

30

40

55

63

75

100

110

147

200

AC-3 380V

Kw

55

75

90

110

132

160

200

150

335

AC-3 660

Kw

80

100

110

129

160

220

280

335

450

Electrical life

AC-3

10000t

60


50




30


20

AC-4

10000t

1.5


1.5




0.8


0.5

Machinery life


10000t

600


600




500


500

Operation Frequency

AC-3

t/h

600


600




300


300

AC-4

t/h

150


150




150


150

Matching fuse type



RT16-160

RT16-200

RT16-250

RT16-315

RT16-400

RT16-400

RT16-500

RT16-630

RT16-800

Matching thermal relay type



LR9-F53






LR9-F73



Wiring capacity


mm²

50

50

95

95

150

185

30X5(2)

40X5(2)

50X5(2)

Coil


Control power voltage (Us)

AC

V

48,110,220,380,440,660

Allowed control circuit voltage

Close

V


Open

V


Coil power

Close

VA

550


800


1200


1200

1250

1650

Keeping

VA

45


55


13


20

24

22

Loss power

W

12~16


18~24


12


14

18

20

Auxiliary contact


Rated heating current (Ith)


A

10

Rated operation voltage (Ue)

AC

V

380

DC

V

220

Rated control capacity

AC-15

VA

360

DC-13

W

33