FNX2-F series Telemechanic Contactor
1. General
FNX2-F series AC contactor is applicable in the circuit rated voltage up to 1000V AC. 50/60Hz, rated current up to 780A, for long distance breaking circuit and frequency starting or controlling the motor. FNX2-F Series Telemechanic Contactor also can be used for the control of distributing circuits of rated current from 200A to 1600A(AC-1)/115A to 780A(AC-3). The products comply with IEC 60947-4.
2. Type designation
Name | Rated current | Auxiliary contact | Pole number | Coil voltage | Frequency |
FNX2-F | 115—780 | — | 3,4 | 48—66 | 50/60 |
Rated current (A) | Auxiliary contact | Type |
Normal open (NO) | Normal close (NC) |
115 | — | — | FNX2-F11500* |
150 | — | — | FNX2-F15000* |
185 | — | — | FNX2-F18500* |
225 | — | — | FNX2-F22500 |
265 | — | — | FNX2-F26500 |
330 | — | — | FNX2-F33000* |
400 | — | — | FNX2-F40000 |
500 | — | — | FNX2-F50000 |
630 | — | — | FNX2-F63000* |
Note: 3 Pole is normal type, not remarked in the type name.
3. Specifications of FNX2-F Series Telemechanic Contactor
Type |
|
| FNX2-F115 | FNX2-F150 | FNX2-F185 | FNX2-F225 | FNX2-F265 | FNX2-F330 | FNX2-F400 | FNX2-F500 | FNX2-F630 |
Main circuit characteristic |
|
Poles | 3P.4P |
Rated operation voltage (Ue) |
| V | 380 600 1000 |
Rated insulation voltage (Ui) |
| V | 1000 |
Rated heating current (Ith) |
| A | 200 | 200 | 275 | 275 | 315 | 380 | 450 | 630 | 800 |
Rated operation current (Ie) | AC-3 380V | A | 115 | 150 | 185 | 225 | 265 | 330 | 400 | 500 | 630 |
AC-3 660V | A | 86 | 108 | 118 | 137 | 170 | 235 | 303 | 353 | 462 |
AC-3 1000V | A | 46 | 51 | 71 | 90 | 112 | 115 | 200 | 232 | 331 |
AC-4 380V | A | 52 | 60 | 79 | 85 | 105 | 117 | 138 | 147 | 188 |
AC-4 660V | A | 49 | 61 | 69 | 82 | 98 | 118 | 135 | 145 | 170 |
Max.power of 3 phase motor controlled | AC-3 220V | Kw | 30 | 40 | 55 | 63 | 75 | 100 | 110 | 147 | 200 |
AC-3 380V | Kw | 55 | 75 | 90 | 110 | 132 | 160 | 200 | 150 | 335 |
AC-3 660 | Kw | 80 | 100 | 110 | 129 | 160 | 220 | 280 | 335 | 450 |
Electrical life | AC-3 | 10000t | 60 |
| 50 |
|
|
| 30 |
| 20 |
AC-4 | 10000t | 1.5 |
| 1.5 |
|
|
| 0.8 |
| 0.5 |
Machinery life |
| 10000t | 600 |
| 600 |
|
|
| 500 |
| 500 |
Operation Frequency | AC-3 | t/h | 600 |
| 600 |
|
|
| 300 |
| 300 |
AC-4 | t/h | 150 |
| 150 |
|
|
| 150 |
| 150 |
Matching fuse type |
|
| RT16-160 | RT16-200 | RT16-250 | RT16-315 | RT16-400 | RT16-400 | RT16-500 | RT16-630 | RT16-800 |
Matching thermal relay type |
|
| LR9-F53 |
|
|
|
|
| LR9-F73 |
|
|
Wiring capacity |
| mm² | 50 | 50 | 95 | 95 | 150 | 185 | 30X5(2) | 40X5(2) | 50X5(2) |
Coil |
|
Control power voltage (Us) | AC | V | 48,110,220,380,440,660 |
Allowed control circuit voltage | Close | V |
|
Open | V |
|
Coil power | Close | VA | 550 |
| 800 |
| 1200 |
| 1200 | 1250 | 1650 |
Keeping | VA | 45 |
| 55 |
| 13 |
| 20 | 24 | 22 |
Loss power | W | 12~16 |
| 18~24 |
| 12 |
| 14 | 18 | 20 |
Auxiliary contact |
|
Rated heating current (Ith) |
| A | 10 |
Rated operation voltage (Ue) | AC | V | 380 |
DC | V | 220 |
Rated control capacity | AC-15 | VA | 360 |
DC-13 | W | 33 |
Relevant Products